电气工程学报 ›› 2023, Vol. 18 ›› Issue (1): 181-187.doi: 10.11985/2023.01.020

• 电力系统 • 上一篇    下一篇

扫码分享

基于特征信号注入的含IIDG配电网谐波差动保护方案

杨立明(), 周浩亮, 朱振洪   

  1. 国网浙江余姚市供电有限公司 余姚 315400
  • 收稿日期:2021-11-11 修回日期:2022-05-06 出版日期:2023-03-25 发布日期:2023-04-19
  • 作者简介:杨立明,男,1976年生。主要研究方向为电力系统继电保护与控制。E-mail:lilyplus@126.com

Harmonic Differential Protection Scheme Based on Characteristic Signal Injection for Distribution Network with IIDG

YANG Liming(), ZHOU Haoliang, ZHU Zhenhong   

  1. State Grid Zhejiang Yuyao Electric Power Co., Ltd., Yuyao 315400
  • Received:2021-11-11 Revised:2022-05-06 Online:2023-03-25 Published:2023-04-19

摘要:

逆变型分布式电源(Inverter interfaced distributed generation,IIDG)接入后,使得配电网成为复杂的多电源系统,也改变了配电网传统的潮流结构、运行方式和故障特性。充分利用IIDG接入对保护的积极因素,构建IIDG并网逆变器主动作用机制,提出基于特征信号注入的含IIDG配电网谐波差动保护方案,通过IIDG的主动参与保护使得保护更具灵活性。以DG并网点电能质量合格且IIDG输出功率不越限为约束,选择于IIDG电流内环注入特征高次谐波信号,并确定了能量主动调控的启用时机和有效作用时段,基于此提出了谐波电流含有率差动保护方案,并通过仿真验证了所提保护方案的合理性。

关键词: 谐波差动保护, 特征信号注入, 逆变型分布式电源, 主动式保护

Abstract:

After the inverter interfaced distributed generation(IIDG) is connected, the distribution network becomes a complex multi-source system, which also changes the traditional power flow structure, operation mode and fault characteristics of the distribution network. Taking advantage of the positive factors of IIDG access to protection, the active action mechanism of IIDG grid-connected inverters is constructed. A harmonic differential protection scheme for distribution network with IIDG based on characteristic signal injection is proposed, which makes the protection more flexible through the active participation of IIDG. Constrained by the power quality of the IIDG PCC point and the output power limit of the IIDG, the characteristic high-order harmonic signal is injected into the inner current loop of the IIDG, and the activation time and effective period of active signal regulation are determined. Based on this, the harmonic current content differential protection scheme is proposed, and the rationality of the proposed protection scheme is verified by simulation.

Key words: Harmonic differential protection, characteristic signal injection, inverter interfaced distributed generation, active protection

中图分类号: