Journal of Electrical Engineering ›› 2018, Vol. 13 ›› Issue (9): 44-49.doi: 10.11985/2018.09.008

Previous Articles    

An Electric Permanent Magnet Motor Operating Mechanism Improvement

Wei Kai,Ma Feng Liu, ,Chen Xu   

  1. Xi’an XD Switchgear Electric Co., Ltd. Xi’an 710077 China
  • Received:2018-07-02 Online:2018-09-25 Published:2019-11-29

Abstract:

This paper describes the problem and improvement measures of the micro circuit breaker in the start-up of an electric actuator permanent magnet motor. Using LabVIEW software to test and analyze the parameters such as current and angle, the reason of the trip is that the design of motor armature resistance is small. The experiment shows that by increasing the armature resistance, the starting current is reduced and the micro-circuit breaker is eliminated, and the operation requirement of the electric actuator is satisfied.

Key words: Electric operating mechanism, permanent magnet motor, miniature circuit breaker, trip

CLC Number: