Analysis of a Maloperation Event of Non Full Phase Protection of 220 kV Circuit Breaker and the Method of Circuit Improvement

ZHANG Bin,LIN Jianxiong,MA Yongchun   

  1. Shantou Power Supply Bureau, Guangdong Power Grid Co., Ltd., Shantou 515041 China
  • Received:2020-01-13 Online:2020-03-25 Published:2020-05-13

Abstract:

Aiming at the malfunction problem of non-full-phase protection of circuit breaker which is frequently happens in the power system, taking the maloperation of non-full-phase protection of a 220 kV line circuit breaker as an example, the causes of maloperation of protection are analyzed in depth. Considering the actual operation and maintenance situation, an improvement method of non-full phase protection circuit based on three pairs of normally open and normally closed auxiliary contacts is proposed. This method is based on the traditional circuit breaker non-full phase protection circuit, which can effectively avoid the misoperation of non-full-phase protection caused by external environment, switching auxiliary contacts and relay faults. Taking a 220 kV standby line A and B circuit breaker body non-full phase protection circuit as an example, the method is proved to be effective and feasible by the experiment.

Key words: Non-full-phase protection, auxiliary contact, relay, insulation, circuit improvement