Journal of Electrical Engineering ›› 2017, Vol. 12 ›› Issue (10): 37-44.doi: 10.11985/2017.10.006

Previous Articles     Next Articles

Analysis and Handling of Coupling Grounding Fault for Multi-Cable Lines in Distribution Network

Ma Zhoujun1,2,Chen Jiankun2,Lan Lan2,Xu Honghua2   

  1. 1. Hohai University Nanjing 210098 China
    2. Nanjing Power Supply Company Nanjing 210019 China
  • Received:2017-02-26 Online:2017-10-25 Published:2017-10-25

Abstract:

Power cable has many advantages such as high reliability, strong power supply capacity, space saving, environmentally friendly and so on. Therefore the penetrance of power cable in city distribution network is increasing. In the paper the successively tripping fault of one particular distribution network multi-cable line is studied. Aiming to one bus, the fault of 10kV multi-cable lines, grounding current of cable shielding layer, and impact of zero sequence current on correct wiring and neutral point earthing of users sides are studied. The coupling grounding fault is analyzed combining time and space, also the occurrence and development of fault is deduced. Finally, some advices are proposed for better operation and dealing with complicated coupling fault.

Key words: Distribution network, multi-cable line, single-phase ground fault, coupling fault, zero sequence current transformer, neutral grounding