Study on Grounding Mode of Neutral Point through Arc Suppression Coil in Parallel with Median Resistance

YE Yuanbo1(), WANG Shenghe1(), HUANG Taigui1(), WEI Lixin2()   

  1. 1. State Grid Anhui Electric Power Co., Ltd., Hefei 230022
    2. Sieyuan Electric Co., Ltd., Shanghai 201108
  • Received:2020-12-20 Revised:2021-10-08 Online:2021-12-25 Published:2022-02-10

Abstract:

The traditional neutral grounding method is easy to lead to over-compensation and under-compensation, and the location error of grounding fault is large. A new neutral grounding method is designed to solve the problem of over-compensation and under-compensation of fault current by using active arc suppression technique and parallel connection of median resistance, single-phase-to-ground fault location based on the weighted multi-source shortest path algorithm (Floyd algorithm) can be used for fault location of multiple transmission lines. Finally, by comparing the maximum fault current curve and error analysis curve of three different grounding modes, it is found that the fault current of the proposed method is the most stable, and the fault current is only between 15 A and 20 A, the maximum error rate of fault location is less than 3%, which proves the superiority of the grounding mode and the feasibility of the design.

Key words: Active arc suppression technology, grounding mode of parallel median resistance, Floyd fault location algorithm