Journal of Electrical Engineering ›› 2021, Vol. 16 ›› Issue (2): 174-180.doi: 10.11985/2021.02.022

Previous Articles     Next Articles

扫码分享

Typical Faults Simulation Analysis and Protection Improvement Suggestions of Niu-cong HVDC Niuzhai Station

DAI Shulong(), ZHANG Rui()   

  1. Qujing Bureau, CSG EHV Power Transmission Company, Qujing 655000
  • Received:2020-06-24 Revised:2021-01-20 Online:2021-06-25 Published:2021-08-05
  • Contact: DAI Shulong E-mail:951508268@qq.com;22121441@qq.com

Abstract:

In order to study the development mechanism of faults and the action characteristics of current protection system in Niu-cong HVDC Niuzhai station theoretical basis for HVDC control protection logic optimization is provided. The typical faults of Niuzhai station in the simulation model of Niu-cong HVDC PSCAD/EMTDC is set up. It is found that the HVDC system can return to normal quickly after eliminating the faults on the grid side of converter transformer of Niuzhai station. The grounding fault of valve side of converter transformer and valve area will results in strong current flowing through the grounding electrode of DC Niuzhai side, short circuit faults will leads to the development of three-phase short circuit in AC side. It points out the disadvantage of the current 50 Hz protection and puts forward the improvement measures. According to the characteristics of valve short-circuit, a new criterion of valve short-circuit protection is proposed, which can form dual protection with the current protection principle, and provide theoretical reference for the design of HVDC engineering protection system in the future.

Key words: Niu-cong HVDC, typical faults, simulation of PSCAD/EMTDC, 50 Hz protection, valve short circuit protection

CLC Number: